Commence normal
central heating mode
until temperature
reaches 20°C
34
There is a delay of 6 seconds,
pump pulses for 2 seconds,
60 second wait,
2 second pump pulse,
60 second wait,
pump pulses for 2 seconds.
OVERRUN FUNCTION
Run pump
4 min ON
30 min OFF
END DHW
DEMAND
END CH
DEMAND
Pump runs
for
3 minutes
AUTOFROSTAT FUNCTION
Monitor
central
heating
sensor
Below
5°C
5°C
to
9°C
Above
9°C
No demand
and primary
temperature
below 8°C
Internal
"Autofrostat"
demand
Return to
normal off
state
Fan low speed
35 seconds
Fan low speed if
primary temp
above 85°C until
below 80°C.
11
Fig. 9. Wiring diagram.
Control Board
Fan
Flame
sense
electrode
Spark
electrode
Spark
Generator
Mains in
Link
Black 6.3mm tag Common
White 4.8mm tag Low Speed
Red 2.8mm tag High Speed
Flow
turbine
ST16
2 blue
2 orange
2 brown
brown
blue
blue
brown
green
2 yellow
2 red
ST2
ST15
ST1
Pump
Gas valve
white
black
Earth tabs
CH
sensor
Air
Pressure
Switch
2 green
white
black
Regulator
Valve
Safety
Valve
red
white
green/yellow
2 violet
Safety
Valve
DHW
sensor
Overheat cut-off device