WALL MOUNTEDDANESMOORWM 12/19ROOM SEALED BF WALL MOUNTEDOIL-FIRED PRESSURE JET APPLIANCEINSTALLATION ANDSERVICING INSTRUCTIONSBOILER OUTPUTHot Water a
10(See Figs. 9, 10 and 11).8.1 The oil storage tank must be installed in accordance withBS799 Part 5. The tank should be arranged with a slope of 1 in
118.11 The following components should be fitted in the fuel linebetween the storage tank and burner:1. A manual isolating valve installed as close to
129.1 The appliance is suitable for connection to fully pumpedconventional indirect hot water systems utilising an indirectdouble feed cylinder. This
13Automatic air ventFig. 13. Typical fully pumped sealed system (Honeywell ‘Y’ plan).ExpansionVesselDivertingvalveBoilerPumpRadiatorN.B. A drain cock
14(See Figs. 15 to 22).10.1 The electrical supply to this appliance must satisfy the latestedition IEE Wiring Regulations and any local regulations wh
15(iii) Honeywell "S" plan. (See Fig. 20, 21, 22)Only the burner will fire. This will allow approximately 3 minutes test time if the boiler
16Fig. 16. Basic control (Room thermostat).NOTE: Remove link 2 to 4.Programmer Conections:Grey (7) - Central HeatingWhite (8) - Domestic hot water
17Fig. 17. Honeywell ‘Y’ Plan - external programmer.NOTE: Remove link 2 to 4.NOTE: Honeywell wiring centre(Part No. 42005748-001) shouldnot be used.br
18Fig. 18. Honeywell ‘Y’ Plan - facia mounted programmer.NOTE: Remove link 2 to 4.Remove orange wire from 9 and relocate to 6.Set the switch on the re
19Fig. 19. Honeywell ‘Y’ Plan - 10 way junction box.NOTE: When using a Worcester facia mount-ed programmer do not wire in this time con-troller. Wire
1.1 This appliance must be commissioned by a competent engineerafter installation. 1.2 General installation information and advice may be obtainedfrom
20Fig. 20. Honeywell ‘S’ Plan - external programmer.NOTE: Remove link 2 to 4.NOTE: Honeywell wiring centre(Part No. 42005748-001) shouldnot be used.Wa
21Fig. 21. Honeywell ‘S’ Plan - facia mounted programmer.NOTE: Remove link 2 to 4.Set the switch on the rear of the programmerto "P".NOTE: H
22Fig. 22. Honeywell ‘S’ Plan - 10 way junction box.NOTE: When using a Worcester facia mount-ed programmer do not wire in this time con-troller. Wire
23The Wall Mounted appliance is installed within the wall of theproperty and is serviced from outside the property, but the engi-neer must have access
11.3 Reassembling the Appliance1. From the outside of the property carefully insert the externalduct into the wall mounting duct with the oil connecti
25Wall mountingbracketFig. 24. Wall mounting bracket positions.Wall MountingBracketWall mountingductWall mountingduct(a) Standard 315mm Position(b) Op
22. Insert the baffle into the heat exchanger ensuring the baffle ispushed hard against the back of the heat exchanger (see fig. 26).23. Check the thr
10. Check all of the air-ways to the burner are clear of anyobstruction.12.5 Check the Burner1. Hang the burner on the burner hanging bracket situate
WARNING: The appliance is serviced and repaired externally.External equipment operated at 230volts should not be ser-viced or repaired under adverse w
29Fig. 28. Electro Oil Inter B9 Burner.(12/19 model)Combustion HeadBlast tubeNozzleNozzle blockElectrode gap3.0 mm8.0 mmCombustion headLocking screwTr
33. Technical DataFig. 1. Pipework dimensions inside the property (all dimensions are millimeters)Table 1SPECIFICATIONSMODEL 12/19POWER SUPPLY 230V 50
30Fig. 31. Mechanical shut-off valve.Fig. 29. Service switch positionsServiceOffRunNote: Always set the switch to run after servicing.Fig. 30. Hanging
31Part Worcester Part No.Stand-off kit (4 inch wall) 7 716 192 256Electrical service lead 7 716 192 301Flue terminal guard kit 7 716 190 017Twin Chann
32LOCKOUTINDICATED BY RED LAMP ON CONTROL BOXTo Re-set press re-set buttonIgnition failure No oil deliveryfrom nozzle.Check oil supplyat oil pump.Air
34
This booklet is accurate at the date of printing but will be superseded and should be disregarded if specifications and/or appearances are changed in
Fig. 2. Internal view of the appliance.PhialretainingspringManual reset high limitthermostatPhialretainingspringDuct manualreset thermostatAutomatic r
5Fig. 3. External view of the appliance.External duct(a) Exploded view(b) Assembled viewHeatexchangerExternal controlbox lockingscrewsInsulation boxFi
6Fig. 4. Appliance position relative to standard wall thickness with cabinet in the standard Position.130mm* 70mm* 55mm315mm315mm 315mm102mm (4 inch)
4.1 The appliance may be installed in any room although partic-ular attention is drawn to the requirements of the current I.E.E.Wiring regulations BS
7.1 The appliance is supplied with a telescopic flue system thatcaters for 102mm (4 inch) to 460mm (18 inch) Wall thickness.For details of the install
Flue outlet Terminal Position Minimum Distance (mm)A Directly below an opening, air brick, window, etc.......... 600B Hori